Primary Fluid Network (PFN)
Primary Fluid Network (PFN) for Liquid-Cooled Data Centers
Facility-side cooling water distribution, engineered, fabricated, and commissioned by RexEdge, built for AI and high-density racks.
The Primary Fluid Network (PFN) is the facility-side water loop that carries heat away from your coolant distribution units (CDUs) to chillers, dry coolers or cooling towers. As AI racks move past 50 kW, the PFN becomes the backbone of the whole liquid cooling system. RexEdge designs, fabricates and installs stainless steel PFN piping that is clean, leak-tight and ready for the next generation of GPUs.
What Is a Primary Fluid Network (pfn) ?
A liquid-cooled data centre runs two water loops. The Primary Fluid Network — also called the facility water system (FWS) in ASHRAE terms — links the heat rejection plant to every CDU in the building. The Secondary Fluid Network (SFN), or technology cooling system, runs from each CDU to the racks and cold plates.
The CDU sits between the two loops. Its heat exchanger keeps facility water away from sensitive IT hardware, so the PFN can carry water or water-glycol while the SFN carries a tightly filtered coolant.
A typical PFN includes:
- Large-bore supply and return headers (usually DN100 and above)
- Branch connections and isolation valves for every CDU
- Pumps, expansion tanks, strainers and air separators
- Flow, pressure and temperature instrumentation tied to the BMS
- Tie-ins to chillers, dry coolers, cooling towers or heat-reuse systems
Materials and engineering standards
Parameter | RexEdge PFN |
|---|---|
Pipe material | SS 304L / SS 316L |
Pipe type | Seamless and ERW |
Joints | Orbital / TIG butt welds, flanged or grooved |
Fluids | Facility water, water-glycol mixes |
Supply temperature | Designed for ASHRAE |
Design pressure | [e.g. up to 10 or 16 bar] |
Testing | Hydrostatic test, radiography / DPT on welds, cleanliness checks |
Documentation | Mill test certificates, weld maps, test reports, as-built drawings |
RexEdge has it’s own manufacturing facilities for stainless steel pipe and tube , so material quality is where we are strongest. Every PFN is built from traceable pipe, fittings and flanges.
Quality Control and Testing
Every Secondary Fluid Network assembly passes the same checks before dispatch:
- Material test certificates traced to heat number for every pipe and fitting.
- Weld inspection, including visual and borescope checks of internal weld beads.
- Hydrostatic pressure testing to specification.
- Helium or pressure-decay leak testing.
- Particle-count flush and cleanliness verification.
- Dimensional check, labeling, end-capping and nitrogen-purged packing.
Plan Your Secondary Fluid Network with RexEdge
Share your rack layout, target density and CDU details. Our engineers will send a technical proposal and budget estimate.
Click HereFREQUENTLY ASKED QUESTIONS (FAQ)
The PFN is the facility-side water loop. It connects heat rejection equipment, such as chillers, dry coolers and cooling towers, to the coolant distribution units (CDUs) that serve the IT racks.
The PFN runs from the cooling plant to the CDUs and carries facility water. The Secondary Fluid Network (SFN) runs from the CDUs to the racks and cold plates and carries a filtered, conditioned coolant. The CDU's heat exchanger keeps the two loops apart.
Yes. ASHRAE calls the primary loop the facility water system (FWS). PFN and FWS describe the same part of the cooling system.
Stainless steel (SS 304L or 316L) resists corrosion, keeps the water clean and needs less treatment over its life. Carbon steel is cheaper up front but needs stricter water chemistry and more maintenance.
It depends on the climate and the equipment. ASHRAE's W-classes range from about 17°C up to 45°C and above. Warmer water allows more free cooling and makes heat reuse easier.
Yes. Many operators add a PFN to bring facility water to new CDUs for direct-to-chip cooling. We survey the site and plan tie-ins to minimise downtime.